MT Transko Bima Alarm and Monitoring Engine Room

MT Transko Bima Alarm and Monitoring Engine Room (2017)

Job

Engine room alarm and monitoring system could not detect the value of all the either sensor temperature, pressure and rpm meter is in the engine room.

History

This problem occurs when the installation of back up power ups for CPU monitoring engine room alarm system.

Job Detail

  1. Check and repair the communication module
    • Cleaning pcb board module
    • Check the performance of the module
  2. Codule includes:
    • Microcomputer substations
    • Power switch
    • Wiring module
    • Power unit
    • I / O panel
    • Output panel
    • Communication module
    • D / A converting module
    • Result
      • All the modules function properly
  3. Check communication cable
    • Check the condition of the socket and termination cord
    • Clean the socket serial port
    • Ensure performance communication cables
    • Result
      • All communication cables function properly
  4. Check cpu unit and engine room alarm monitoring program
    • Monitoring and alarm system has two cpu (computer industry) with label UO101 and UO201

Action taken



  • Cleaning CPU and every card that are inside
  • Check the performance of each card CPU

Checking results:

  1. Computer industry label UO101
    • Found ethernett card problem
    • Not connected the communication between industrial computer with modules (4 modules are connected, 4 module is not connected)
  2. Computer industry label UO201
    1. Computer problems (hang)

Solution :

  • We take the ethernet card in the computer industry UO201 label and installing in the computer industry UO101 label (no spare ethernet card on board)

Result

  • Industrial computer can communicate with all modules (8 module connected) but the monitoring and alarm system can not function because the necessary configuration settings for communication each module and for configuration settings through a password dialog box. we need a password to enter the configuration settings

Documentation

MT Transko Bima Alarm and Monitoring Engine Room Communication Diagnosis After Replacing the Ethernet Card
MT Transko Bima Alarm and Monitoring Engine Room Communication Diagnosis After Replacing the Ethernet Card
MT Transko Bima Alarm and Monitoring Engine Room Communication the Initial Diagnosis
MT Transko Bima Alarm and Monitoring Engine Room Communication the Initial Diagnosis
MT Transko Bima Alarm and Monitoring Engine Room Ethernet Card Problem
MT Transko Bima Alarm and Monitoring Engine Room Ethernet Card Problem
MT Transko Bima Alarm and Monitoring Engine Room Password Dialog Box
MT Transko Bima Alarm and Monitoring Engine Room Password Dialog Box

MT Transko Bima

MT Transko Bima
MT Transko Bima